17.3
Refresh Setting
Set refresh parameters.
Window
Displayed items
Item
Link Side
MELIPC side
Target
device name
Points
Start
End
17 BASIC PARAMETERS
182
17.3 Refresh Setting
Description
The number of points for the link devices (RX/RY, RWr/RWw) for the
number of occupied stations and start/end device number set in the network
configuration settings are displayed.
The target for link refresh is displayed.
Set the device of the link refresh target.
The number of device points subject to link refresh is displayed. (A value the
same as the number of points of the link side is displayed. )
Set the start device number within the link refresh range.
The end device number within the link refresh range is displayed.
Setting range
Specify Device
M, B, D, W, ZR
• M: 0 to 61439
• B: 0 to 9FFFFH
• D: 0 to 4184063
• W: 0 to FFFFFH
• ZR: 0 to 524287