Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 222

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Appendix 2
When an error is detected by the self-diagnosis function, the error code is stored to a special register (SD). Additionally, if an
error occurs during a communication request from either MI Configurator or the network system to this product, the error code
is returned to the request source.
This section shows the details of errors that occur in this product and their corrective actions.
Check of error codes
An error code can be checked with the following methods
If multiple errors have occurred at the same time, then these will be handled from the oldest first according to
their history date.
Checking error codes with MI Configurator
Codes of errors that are occurring on the MELIPC can be checked using the MELIPC diagnosis of MI Configurator.
[Diagnostics]  [MELIPC Diagnostics]
Checking by the dot matrix LED
Codes of errors that occurred can be checked using [Error code] of menu selection mode.
(MELIPC MI5000 Series User's Manual (Startup))
Checking by a user program
Error codes can be acquired by C Controller module dedicated functions. In addition, the acquired error codes can be
checked by the user program outputting them to the dot matrix LED or monitor. (MELIPC MI5000 Series Programming
Manual (VxWorks))
Error code system
Error codes are represented in four-digit hexadecimal number (unsigned 16-bit integer).
Errors that can be detected by the self-diagnosis function and common errors that can be detected during data
communications between modules are included in the following table.
Error detection type
Detection by self-diagnosis
Detected during communication
between CPU modules
Detection by self-diagnosis
Detected during communication
between CPU modules
APPX
220
Appendix 2 List of Error Codes
List of Error Codes
range
Description
1000H to 3FFFH
Error code specific to each module, such as self-diagnostic errors
4000H to 4FFFH
Errors related to AnU/QnA/Qn Series programmable controller CPU general data
5000H to 5FFFH
Errors related to general data of slice I/O modules
7000H to 7FFFH
Errors related to general data of AnU/QnA/Qn Series intelligent function modules
8000H to 8FFFH
Errors related to CC-Link IE Field Network function
9000H to 9FFFH
A000H to AFFFH
B000H to BFFFH
Error in CC-Link module
C000H to CFBFH
Error in Ethernet module
CFC0H to CFFFH
CC-Link IE Field Network Basic errors
D000H to DFFFH
Error in CC-Link IE Field Network module
E000H to EFFFH
Error in CC-Link IE Controller Network module
F000H to FFFFH
Error in MELSECNET/H network modules or MELSECNET/10 network module

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw