Description CDH EGD fault detected by the T processor
Possible Cause
CDH EGD producer is powered down
Producer is unhealthy
Ethernet connection(s) failure
Solution
Ensure all EGD producers are powered up and healthy.
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
Replace the producer processor module.
496
Description

Failed to incorporate the user-configured frame state timeouts

Possible Cause
Invalid user-configured frame state timeout values
Failed to parse the user-configured frame state timeouts file
Solution
Timeout values configured by the user must satisfy the condition
Frame Rate > Output Timeout > App Timeout > Input Timeout > 0.
Rebuild the application and force an offline download of the application to the controller.
497-498
Description

Fan loss detected for controller fan [ ]

Possible Cause
Hardware malfunction
Fan power not applied
Solution
Check the fan.
Verify that the power connector is properly inserted.
Replace the fan.
64
GEH-6855_Vol_II