9.3.6.3 RS-422
There is the need to provide a termination resistor at either end of a transmission line.
SSCA provides selectable termination resistors for each pair of signal lines.
Jumpers JP#A and JP#B apply or remove the termination resistors between signals A-B and C-D.
Above Point 3 function is repeated for each serial communication channel. The default jumper position is to disconnect
the termination resistor.
The SSCA is clearly marked to display the relationship of the termination jumpers and the serial communication channel
signals.
The configuration at SSCA jumper (JP#A, JP#B set to IN) must match the ToolboxST configuration as displayed in the
following diagram. The 120 Ω resistance selection is used as an example.
Channel
SCOM
Channel 1
26
Channel 2
25
Channel 3
13
Channel 4
14
Channel 5
02
Channel 6
01
Protocol
A
RS-422
TX+
RS-485
TX/RX+
RS-232C
DTR/RTS
298
GEH-6855_Vol_II
Terminal Board Screw Connections
A
B
28
30
27
29
15
17
16
18
04
06
03
05
B
C
TX-
RX+
TX/RX-
Jumper from A
TX
CTS
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
C
32
31
19
20
08
07
D
Cable Length
RX-
Up to 305 m (1000 ft)
Jumper from B
Up to 305 m (1000 ft)
RX
Up to 15 m (50 ft) or 2500 pF
Public Information
D
RET
34
36
33
35
21
23
22
24
10
12
09
11