Jpdc-Ac [ ]V Fdbk (Jac Connector) Out Of Range; Jpdc-Fuse Fuac1 (Jac1 Connector) Is Blown Or Swac1 Switched Off - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

181
Description JPDC-AC [ ]V fdbk (JAC connector) out of range.
Possible Cause
The specified ac input is configured to the wrong nominal voltage value.
The ac input voltage is out of tolerance from the nominal voltage value.
The ac source voltage is out of range.
The ac input is not connected.
Solution
Verify that the nominal ac input voltage matches the value configured in ACFdbkInVoltage.
The ac tolerance is set too low. Verify that ACFdbkInTol is set to the proper value.
Verify that the ac supply is within the specified parameters. Refer to the JPDC help documentation.
If the ac input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (AC_VFdbk1_Volt) to Disabled.
182
Description JPDC-Fuse FUAC1 (JAC1 connector) is blown or SWAC1 switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The ac input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the ac input connections to the terminal board.
If the ac input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (AC_VFdbk1_Volt) to Disabled.
350
GEH-6855_Vol_II