8.3.1.3 Tracking Filters

The following table defines differences in the tracking filters with versions of the I/O pack.
Item
Center frequency
Filter roll off
1X / 2X channels
8.3.1.4 Wideband Filters & Velocity Conditioning
The following table defines differences in the Wideband Filters & Velocity Conditioning with versions of the I/O pack.
Item
Supported Sensors
Maximum octave attenuation
Output of wideband filter
Notes

8.3.1.5 CDM Sensors

YVIBS1B adds support for CDM sensors. From the Parameters tab, CDM_scan_period is a selectable scan period for
CDM sensor inputs.
Item
Supported sensors
Maximum octave attenuation
Output of wideband filter
Scan period selection
LM 1x tracking filter support

8.3.2 Vibration Monitoring Firmware

The following subsections provide details for common firmware features using in vibration monitoring applications. For
application-specific firmware use cases and procedures, refer to the section
236
GEH-6855_Vol_II
YVIBS1B
-3dB bandwidth correctly matches configuration settings to meet application requirements
Window attenuation increased to -36 dB / octave to meet application requirements
Can base phase measurements off of channel 12 or 13
YVIBS1B
Velomitors, Seismics & LM Accelerometers with integrated outputs
-60 dB for all filter configurations
Can either be assigned to an RMS calculation or Peak-to-peak algorithm, using
Peak-to-peak algorithm and RMS calculation use a Scan time of data. Update rate is equal Frame
Rate.
ISO for Vibration calls for RMS calculations
YVIBS1B
Inputs 1-8 support the following:
Bently Nevada CDM Sensor (CDM_BN_ChgAmp)
PCB CDM Sensor (CDM_PCB_ChgAmp)
-60 dB for all filter configurations
Can either be assigned to an RMS calculation or Peak-to-peak algorithm, using VIB_CalcSel
Peak-to-peak or RMS scan period configured by the CDM_Scan_Period parameter.
Peak-to-peak output supported for up to 3 frequency selections (Inputs 1-3 only)
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Vibration Monitoring Application
VIB_CalcSel
Examples.