8.3.4.10 Gap 9-11

[ ] = defaults
Name
Direction
GAP9_POS1
AnalogInput
GAP10_POS2
AnalogInput
GAP11_POS3
AnalogInput
GnBiasOvride
Snsr_Offset
Gain Bias
Amount of bias
Override
voltage (dc) to
[Disable], Enable
remove from
input signal used
to max. A/Ds
signal range
used only when
GnBiasOvride is
enabled
[10]
±13.5
SysLim2Enabl
Enable System Limit 2
[Disable], Enable
268
GEH-6855_Vol_II
Data
Description
Type
REAL
Average Air Gap,DC
component of input#9
REAL
Average Air Gap,DC
component of input#10
REAL
Average Air Gap,DC
component of input#11
Gain
SysLim1Enabl
Resolution of
Enable System
input signal (net
Limit 1
gain unchanged),
[Disable], Enable
select based on
expected range,
use only if
GnBiasOvride is
enabled
[1x], 2x, 4x, 8x
SysLim2Latch
Latch the alarm
[Latch], NotLatch
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
VIB_Type2
Scale
Volts/mil
Sensor Type, group
or
2
Volts/ips
[Unused],
[0.2]
PosProx
0 to 2
SysLim1Latch
Latch the alarm
[Latch], NotLatch
SysLim2Type
System Limit 2 Check Type
[ >= ] , <=
Public Information
Scale_Off
TMR_
DiffLimit
Scale offset
Difference
for Prox
Limit for Voted
position
TMR Inputs in
only, in mils
Volts or Mils
[0]
[2]
0 to 90
-100 to 100
SysLim1Type
SysLimit1
System Limit 1
System Limit 1 –
Check Type
GAP in negative
[ >= ] , <=
volts (Velomitor)
or positive mils
(Prox)
[90]
-100 to 100
SysLimit2
System Limit 2 – GAP in
negative volts (Velomitor) or
positive mils (Prox)
[10]
-100 to 100