6.8.3 Specifications
Item
Number of Relay Channels
Rated Voltage on Relays
Max Load Current
Max Response Time On
Max Response Time Off
Contact Material
Contact Life
Fault Detection
Size
IS400WROBH1A Option Board
Powered Output Circuits
IS400WROFH1A Option Board
Fused Output Circuits
IS400WROGH1A Option Board
Powered Output Circuits
YDOA Discrete Output Modules

SRLY Specification

12 Form-C relays (12 DO)
Nominal 24, 48, or 125 V dc
Nominal 120 or 240 V ac
0.6 A for 125 V dc operation
1.2 A for 48 V dc operation
2.25 A for 24 V dc operation
2.25 A for 120/240 V ac, 50/60 Hz operation
25 ms typical
25 ms typical
Silver cad-oxide
Electrical operations: 100,000
Mechanical operations: 10,000,000
Relay position feedback using contact pair separate from load contacts.
15.9 cm high x 17.8 cm wide (6.25 in x 7.0 in)
6 fused, associated with relays 1-6, fed from parallel connectors JF1 and
JF2. Both sides of the power source are fused for each output.
1 unfused, associated with relay 12, fed from connector JG1
12 fused circuits, one per relay
12 fused circuits, one associated with each relay. Single side fusing of the
power is associated with the power input on JF1 pin 1. Return power path
through JF1pin 3 is not fused.
Public Information
GEH-6855_Vol_II System Guide 169