Jpdc-Fuse Fuac2 (Jac2 Connector) Is Blown; Jpdc-P28V-R Volt Fdbk (Jr/Pr Connector) Out Of Range - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

183
Description JPDC-Fuse FUAC2 (JAC2 connector) is blown.
Possible Cause
The specified fuse is blown.
The ac input is not connected.
Solution
Replace the fuse.
Verify the ac input connections to the terminal board.
If the ac input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (AC_VFdbk1_Volt) to Disabled.
184
Description JPDC-P28v-R volt fdbk (JR/PR connector) out of range.
Possible Cause
The 28 V power supply input is out of range. It should be within ±5% of 28 V.
The 28 V power supply has not been connected.
There may be a power supply problem.
Solution
The input is not used. Set PS28vEnable to Disable.
Verify the power supply connections (specified connector) to the terminal board.
Verify that the power supply feedback on the JPDC Inputs tab in the ToolboxST configuration is within the expected
tolerance (±5%).
PDM Power Distribution Modules
Public Information
GEH-6855_Vol_II System Guide 351