Low_Input, Low_Value, High_Input, High_Value settings are used by the YUAA firmware to define the linear relationship between mA and customer-defined engineering
units. The I/O Point value will be in Engineering units. Engineering units are specific to the field device being used.
Hart_Enable
‡
Hart_CtrVars
Enable Hart protocol on
Number of control vars to
this channel
read from Hart device
Set to zero if not used.
{Enable}
{0}
Disable
0-5
202
GEH-6855_Vol_II
Low_Value
High_Input
High_Value
Low Input in
Input MA at
High Input in
Engineering
High Value
Engineering
Units
Units
{0}
{20}
{100}
Current Inputs (continued)
Hart_ExStatus
Number of extended status
bytes to read from Hart
device
Set to zero if not used.
{0}
0-26
InputFilter
ExternPwrEnab
Filter
Enable External
Bandwidth in
Power for 4-20ma
Hz
inputs
0.75hz
Disable {Enable}
1.5hz
12hz
3hz
6hz
{Unused}
Hart_MfgID
Hart_DevType
Hart Field Device -
Hart Field Device - Device
Manufacture ID
Type
Note: For HART7 field
Note: For HART7 field
devices, this is the upper
devices, this is lower byte
byte of Expanded Device
of Expanded Device Type
Type
A diagnostic alarm is sent
if the field device ID differs
from this value and the
value is non-zero. This
value can be uploaded
from the YUAA if the field
device is connected.
(Right-click on device
name and select Update
HART IDS)
{0}
{0}
0-255
0-255
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II