Configuration File Load Error - Invalid File Length; Firmware Load Error - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

266
Description

Configuration file load error - invalid file length

Possible Cause
During commissioning or maintenance:
The configuration file in the I/O pack or module does not have the correct size to match the application code that is
loaded.
During normal operation:
Hardware failure
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application. Rebuild the application and download the firmware and the
application code to the affected I/O pack or module.
During normal operation:
Replace the I/O pack or module.
267
Description

Firmware Load Error

Possible Cause
During commissioning or maintenance:
Incompatible version of firmware downloaded
During normal operation:
There is a hardware failure.
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application.
Ensure that each I/O pack or module is upgraded to the latest version. From the ToolboxST application, right-click each
I/O pack or module and selecting Upgrade.
Rebuild the application and download the firmware and the application code to the affected I/O pack or module.
During normal operation:
Replace the I/O pack or module.
Common I/O Module Functionality
Public Information
GEH-6855_Vol_II System Guide 455