Tbci Installation - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

5.4.1 Compatibility
The TBCI supports simplex, dual, and TMR redundancy. One, two, or three I/O packs can be plugged directly into the TBCI.
Version
Wetting Voltage
TBCIS2C
24 V dc
TBCIS3C
48 V dc

5.4.2 TBCI Installation

Connect the wires for the 24 dry contact inputs directly to two I/O terminal blocks on the terminal board. These blocks are
held down with two screws and can be unplugged from the board for maintenance. Each block has 24 terminals accepting up
to #12 AWG wires. A shield terminal strip attached to chassis ground is located immediately to the left of each terminal
block.
In a Simplex system, connect the I/O pack into the TBCI connector JR1. In a Dual system, plug the I/O packs into JR1 and
JS1. In a TMR system, plug the I/O packs into JR1, JS1, and JT1. The I/O pack(s) attach to side-mounting brackets. One or
two Ethernet cables plug into the I/O packs. Connect TBCI to the contact excitation voltage source using plugs JE1 and JE2.
122
GEH-6855_Vol_II
Hazardous Locations Capability
Class 1, Div 2 / Class 2, Zone 2 / ATEX
For ratings and further details, refer to the
Mark VIeS Functional Safety System
Equipment in Hazardous Locations
(HazLoc) Instruction Guide (GEH-6861).
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
IEC61508 certified
with YDIA pack
Yes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents