Ionet-Egd Signal Inputs Are Not Being Updated; Memory Validation Failed - Data Structures; Firmware/Io Configuration Incompatible; Incorrect Or Missing Acquisition Board On Hssl Link 1 - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

371
Description IONet-EGD signal inputs are not being updated
Possible Cause
During commissioning or maintenance:
The I/O pack or module application process is not providing system signal inputs to EGD every frame.
Solution
During commissioning or maintenance:
Rebuild and download the firmware and application code.
Verify that the idle time is adequate for the I/O pack or module, and that the frame rate does not exceed defined limits.
If the problem persists, replace the I/O pack or module.
372
Description Memory Validation failed - Data structures
Possible Cause Hardware memory failure (process data that should not change after the controller goes online was
modified)
Solution
Replace the I/O pack or module.
373
Description Firmware/IO Configuration Incompatible
Possible Cause
I/O pack or module configuration files are incompatible with the firmware (files do not contain
necessary revision)
Solution
During commissioning or maintenance:
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
During normal operation:
Replace the I/O pack or module.
445
Description

Incorrect or Missing Acquisition Board on HSSL link 1

Possible Cause
The acquisition board on High Speed Serial Link 1 is not connected or does not agree with the
ToolboxST configuration.
Solution
Verify that the correct acquisition board is connected to the specified HSSL connector on the UCSA.
Verify that the ToolboxST configuration for the appropriate HSSL connector matches the hardware.
470
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information