206 – 207
Description JPDG ACIn-[ ] [ ]V fdbk (JAC1 connector) out of range
Possible Cause
The specified ac input is configured to the wrong nominal voltage value.
The ac input voltage is out of tolerance from the nominal voltage value.
The ac source voltage is out of range.
The ac input is not connected.
Solution
Verify that the nominal ac input voltage matches the value configured in the ACFdbkInVoltage.
The ac tolerance is set too low. Check that the ACFdbkInTol is set to the proper value.
Verify that the ac supply is within the specified parameters.
If the ac input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the associated
input (AC_Fdbk#_Volt) to Disabled.
208
Description JPDG DC 24V Voltage fdbk mag (JPS1/JPS2 connector) out of range
Possible Cause
The 24/48 V dc input is less than the DC_24v_Trig_Volt.
The DC_24v_Trig_Volt is set too high.
The 24/48 V dc source voltage is out of range.
The 24/48 V dc input is not connected.
Solution
Verify that the DC_24v_Trig_Volt is set correctly.
Check the connections to the specified connector.
Check the grounding of the dc input signals.
If 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to Disabled.