8.3.4.2 Variables
Variables
Description
L3DIAG_YVIB_x
I/O Pack Diagnostic Indicator where R, S, or T is the redundancy of pack
LINK_OK_YVIB_
IONet Link Okay Indicator where R, S, or T is the redundancy
x
ATTN_YVIB_x
I/O Pack Status Indicator where R, S, or T is the redundancy
PS18V_YVIB_x
I/O Pack 18 V Power Supply Indication where R, S, or T is the redundancy
PS28V_YVIB_x
I/O Pack 28 V Power Supply Indication where R, S, or T is the redundancy
IOPackTmpr_
I/O Pack Temperature at the processor where R, S, or T is the redundancy
RPM_KPH1
Speed (RPM)of KP#1,calculated from input#13
LM_RPM_A
Speed A(RPM), calculated externally to the I/O Pack
LM_RPM_B
Speed B(RPM), calculated externally to the I/O Pack
LM_RPM_C
Speed C(RPM), calculated externally to the I/O Pack
SysLim1GAPx
Boolean set TRUE if System Limit 1 exceeded for Gap x input
where x = 1 to 13
SysLim2GAPx
Boolean set TRUE if System Limit 2 exceeded for Gap x input
where x = 1 to 13
SysLim1VIBx
Boolean set TRUE if System Limit 1 exceeded for Vib x input
where x = 1 to 8
SysLim2VIBx
Boolean set TRUE if System Limit 2 exceeded for Vib x input
where x = 1 to 8
SysLim1ACCx
Boolean set TRUE if System Limit 1 exceeded for Accelerometer x input
where x = 1 to 9
SysLim2ACCx
Boolean set TRUE if System Limit 2 exceeded for Accelerometer x input
where x = 1 to 9

8.3.4.3 Probe Nominal Settings

Probe Type
Proximity
Seismic
Velomitor
Accelerometer
Keyphasor
Bently Nevada CDM
PCB CDM
These are the default settings used if GnBiasOvride=Disable.
YVIB Vibration Monitor Modules
Gain
Snsr_Offset (Vdc)
1x
9
4x
0
2x
12
2x
10
1x
9
2x
10
2x
-12
Public Information
Direction and
Datatype
Input BOOL
Input BOOL
Input BOOL
Input BOOL
Input BOOL
Input BOOL
Analog Input REAL
Analog Output REAL
Analog Output REAL
Analog Output REAL
Input BOOL
Input BOOL
Input BOOL
Input BOOL
Input BOOL
Input BOOL
Scale (typical value)
200 mv/mil
150 mv/ips
100 mv/ips
150 mv/ips
200 mv/mil
170 mv/psi
170 mv/psi