Total Current Varies From Reference Current; Commanded Current Fdbk Error; Suicide Relay Non-Functional - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

70-71
Description Output [ ] Total current varies from reference current
Possible Cause The difference between the commanded output current and total feedback is greater than TMR_
SuicLimit.
Field wiring problem
Open-circuit on output or total loop resistance is too high
Command is beyond the range of the output.
Solution
Check field wiring and device.
Verify that the value of TMR_SuicLimit is set correctly.
Verify that commanded output is within output range.
74-75
Description Output [ ] commanded current fdbk error
Possible Cause The difference between the commanded output current and current feedback on the terminal board is
greater than D/A_ErrLimit (%).
Open-circuit on output
Terminal board output jumper (JPO) setting is incorrect (for output 1).
Command is beyond the range of the output.
Solution
Check the field wiring and device.
Check the JPO jumper setting on the terminal board.
Verify that the value of D/A_ErrLimit is set correctly.
Verify that the commanded output is within output range.
Replace the I/O pack.
82-83
Description Output [ ] Suicide relay non-functional
Possible Cause The analog output suicide relay command doesn't match the feedback.
Relay failure on the acquisition board.
Hardware failure
Solution Replace the I/O pack.
YAIC Analog I/O Modules
Public Information
GEH-6855_Vol_II System Guide 103