489
Description EGD Error - One or more consumed exchanges contain unbound variables
Possible Cause
An EGD variable has been removed from a Producer's EGD configuration
An EGD variable has been added to a different Producer's EGD Page from its original EGD Page
Solution
Add the offending variable to the Producer's EGD configuration, compress the Page and download the application to the
Producer.
Remove the reference to the offending variable from the Consumer's application code; build and download application to
the Consumer.
Compress the EGD Page in the Producer where the variable has been added; build and download the application to the
Producer.
490
Description Software watchdog has been disabled
Possible Cause
A runtime malfunction has disabled the software watchdog protective function
An invalid version of firmware has been downloaded
Solution
Reload base load, firmware, and application and restart.
If using a UCSA, reformat the flash and reload the firmware.
I/O pack or module: re-download the base load.
If this does not work, replace the controller or I/O module.
491
Description Hardware watchdog has been disabled
Possible Cause
A runtime malfunction has disabled the hardware watchdog protective function
A hardware failure has disabled the hardware watchdog protective function
Solution
Reload firmware and restart.
If problem persists, replace hardware.