GE Mark VIeS System Manual page 459

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

277
Note This alarm is obsolete.
Description IONET-EGD - Exchange [ ] Signature mismatch from Producer [ ], expected [ ], received [ ]
Possible Cause Message version mismatch
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
278
Note This alarm is obsolete.
Description IONET-EGD - Producer [ ] gave bad length Exchange [ ], expected [ ], got [ ]
Possible Cause Exchange message wrong length
Solution
Restart the I/O pack or module.
Upgrade the I/O pack or module firmware and application code.
If the problem persists, replace the I/O pack or module.
279
Description
Could not determine platform type from hardware
Possible Cause
During commissioning or maintenance, there is an incorrect firmware version or hardware malfunction (firmware could
not recognize host hardware type)
During normal operation, there is a hardware failure
Solution
Verify that all connectors are aligned properly and fully seated.
Check the firmware version for compatibility with platform. If it is correct, replace the I/O pack or module.
Common I/O Module Functionality
Public Information
GEH-6855_Vol_II System Guide 459