8.3.4.7 Vib 1-8

[ ] = defaults
Name
Direction
Data
Type
VIB1
AnalogInput
REAL
VIB8
AnalogInput
REAL
Vib_RMS is only valid when OperatingMode is Enhanced and when using YVIBS1B.
fltrlpattn
Filtrlpcutoff
Slope or
Low Pass 3db
attenuation of
point (cutoff in
high pass filter
Hz)
[500]
after cutoff
[2-pole],
15 to 4300
4-pole,
6-pole,
8-pole,
10-pole
SysLim2Enabl
Enable System Limit 2
[Disable], Enable
YVIB Vibration Monitor Modules
Description
Vibration displacement (pk-pk)
or velocity (pk), AC component
of input#1
Vibration displacement (pk-pk)
or velocity (pk), AC component
of input#8
fltrlppattn
Slope or
attenuation of
low pass filter
after cutoff
[2-pole]
4-pole,
6-pole,
8-pole,
10-pole
SysLim2Latch
SysLim2Type
Latch the alarm
System Limit 2 Check
[Latch], NotLatch
Type
[ >= ], <=
Public Information
VIB_CalcSel
TMR_DiffLimt
Difference Limit
for Voted TMR
[ VIB_Pk-Pk ]
Inputs in Volts or
Vib_RMS
Mils
[2]
-100 to 100
SysLim1Enabl
SysLim1Latch
Enable System
Latch the alarm
Limit 1
[Latch], NotLatch
[Disable], Enable
SysLimit2
System Limit 2 – GAP in negative volts (Velomitor)
or positive mils (Prox)
[0]
-100 to 100
Filter
Filtrhpcutoff
Type
Filter
used for
Velomitor
and
Seismic
High Pass 3db
only
point (cutoff in Hz)
[None],
[6]
Low
4 to 300
Pass,
High
Pass,
Band
Pass
SysLim1Type
SysLimit1
System Limit 1
System Limit 1 –
Check Type
GAP in negative
[ >= ], <=
volts (Velomitor)
or positive mils
(Prox)
[50]
-100 to 100
GEH-6855_Vol_II System Guide 265