44, 47
Description JPDS-[ ] P28v-R aux output fuse (JAR connector) not OK
Possible Cause
The auxiliary output JAR fuse has exceeded its current rating (1.6 A at 20°C) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 1.6 A.
The fuse is self-resetting. Refer to help documentation.
45, 48
Description JPDS-[ ] P28v-S aux output fuse (JAS connector) not OK
Possible Cause
The auxiliary output JAS fuse has exceeded its current rating (1.6 A at 20°C) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 1.6 A.
The fuse is self-resetting. Refer to help documentation.
46, 49
Description JPDS-[ ] P28v-T aux output fuse (JAT connector) not OK
Possible Cause
The auxiliary output JAT fuse has exceeded its current rating (1.6 A at 20°C) and disabled the auxiliary output.
Solution
Disconnect the auxiliary output connections and troubleshoot the loading of the auxiliary output beyond 1.6 A.
Fuse is self resetting. Refer to help documentation.