Weak-End Infeed Logic - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
15.2.3.2
15.3
15.3.1
15.3.2
Bay control REC670 2.2 ANSI
Application manual
Set tDelayRev timer at the maximum reset time for the communication equipment that
gives the carrier receive (CRL) signal plus 30 ms. A minimum setting of 40 ms is
recommended, typical 60 ms.
A long tDelayRev setting increases security against unwanted tripping, but delay the
fault clearing in case of a fault developing from one line that evolves to the other one.
The probability of this type of fault is small. Therefore set tDelayRev with a good
margin.
Set the pick-up delay tPickUpRev to <80% of the minimum sum of breaker operate
time + communication delay time, but with a minimum of 20 ms.

Weak-end infeed logic

Set WEI to Echo, to activate the weak-end infeed function with only echo function.
Set WEI to Echo&Trip to obtain echo with trip.
Set tPickUpWEI to 10 ms, a short delay is recommended to avoid that spurious carrier
received signals will activate WEI and cause unwanted carrier send (ECHO) signals.
When single pole tripping is required, a detailed study of the voltages
during phase-to-phase and phase-to-ground faults should be done, at
different fault locations.
Local acceleration logic ZCLCPSCH
Identification
Function description
Local acceleration logic
Application
The local acceleration logic (ZCLCPSCH) is used in those applications where
conventional teleprotection scheme is not available (no communication channel), but
the user still require fast clearance for faults on the whole line.
Scheme communication
IEC 61850
IEC 60617
identification
identification
ZCLCPSCH
-
Section 15
M13856-10 v7
SEMOD52894-1 v4
M14860-1 v4
ANSI/IEEE C37.2
device number
-
M13821-3 v3
477