Interlocking for bus-section disconnector A1A2_DC (3)

Application
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one
bus-section disconnector between section 1 and 2 according to figure 146. A1A2_DC
(3) function can be used for different busbars, which includes a bus-section
disconnector.
WA1 (A1)
189G
ANSI04000492 V1 EN-US
Figure 146:
Switchyard layout A1A2_DC (3)
The signals from other bays connected to the module A1A2_DC are described below.
Signals in single breaker arrangement
If the busbar is divided by bus-section disconnectors, the condition no other
disconnector connected to the bus-section must be made by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding
signals from busbar B are used.
Section 1
(WA1)A1
(WA2)B1
(WA7)C
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
AB_TRAFO
ANSI04000493 V1 EN-US
Figure 147:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
WA2 (A2)
52
A1A2_DC
en04000492_ansi.vsd
Section 2
A2
B2
ABC_BC
ABC_LINE
1MRK 511 401-UUS A
289G
A3
B3
C
AB_TRAFO
en04000493_ansi.vsd
Bay control REC670 2.2 ANSI
Application manual
IP14159-1 v2
M13544-3 v7