Advertisement

Section 14
Control
14.4.8
14.4.8.1
14.4.8.2
404

Interlocking for double CB bay DB (3)

Application
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A
(3), DB_BUS_B (3) and DB_LINE (3) functions are used for a line connected to a
double busbar arrangement according to figure 167.
189
189G
DB_BUS_A
152
6189
989
989G
ANSI04000518 V1 EN-US
Figure 167:
Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined.
DB_BUS_A (3) handles the circuit breaker QA1 that is connected to busbar WA1 and
the disconnectors and grounding switches of this section. DB_BUS_B (3) handles the
circuit breaker QA2 that is connected to busbar WA2 and the disconnectors and
grounding switches of this section.
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE and
DB_BUS_B must be used.
Configuration setting
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
289
252
289G
6289
1MRK 511 401-UUS A
WA1 (A)
WA2 (B)
489G
DB_BUS_B
589G
389G
DB_LINE
en04000518_ansi.vsd
Bay control REC670 2.2 ANSI
Application manual
IP14167-1 v2
M13585-3 v10
M13584-4 v4
M13584-6 v5