Setting Guidelines - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 14
Control
14.8.3
14.9
458
It is especially intended to be used in the interlocking station-wide logics. To be able to
get the signals into other systems, equipment or functions, one must use other tools,
described in the Engineering manual, and define which function block in which
systems, equipment or functions should receive this information.
More specifically, DPGAPC function reports a combined double point position
indication output POSITION, by evaluating the value and the timestamp attributes of
the inputs OPEN and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs
determine the two-bit integer value of the output POSITION. The timestamp of the
output POSITION will have the latest updated timestamp of the inputs OPEN and
CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to
intermediated state.
When the value of the input signal VALID changes, the timestamp of the output
POSITION will be updated as the time when DPGAPC function detects the change.
Refer to Table
44
for the description of the input-output relationship in terms of the
value and the quality attributes.
Table 44:
Description of the input-output relationship
VALID
OPEN
0
-
1
0
1
1
1
0
1
1

Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.
Single point generic control 8 signals SPC8GAPC
CLOSE
Value
-
0
0
0
0
1
1
2
1
3
Bay control REC670 2.2 ANSI
1MRK 511 401-UUS A
POSITION
Description
Intermediate
Intermediate
Open
Closed
Bad State
SEMOD55398-5 v4
SEMOD176448-1 v3
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents