ABB REC670 Applications Manual page 525

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual
132kV Busbar
200/5
31.5 MVA
P
500/5
33kV Busbar
ANSI09000040 V1 EN-US
Figure 208:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 208, it is
necessary to do the following:
1.
Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
(see Section
"Setting of the phase reference
analog input channels
2.
Connect, in PCM600, measurement function to LV side CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the
following table 49:
IED
Q
V
AB
33kV 120V
/
3
3
ANSI09000040-1-en.vsd
channel") data using PCM600 for
Section 17
Monitoring