Wye connected three-phase CT set with its wye point away from the protected object
Bay control REC670 2.2 ANSI
Application manual
C
IC
IB
IA
In the example, everything is done in a similar way as in the above described example
(Figure 13). The only difference is the setting of the parameter CTStarPoint of the used
current inputs on the TRM (item 2 in Figure
CTprim=600A
CTsec=5A
CTWyePoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameter as
set in this example will negate the measured currents in order to ensure that the
currents are measured towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the three-phase CT set
connected to the IED as shown in Figure 14.
IED
2
3
1
14
and 13):
Section 4
Analog inputs
4
SMAI_20_2
BLOCK
AI3P
REVROT
AI1
^GRP2_A
5
AI2
^GRP2_B
AI3
^GRP2_C
AI4
^GRP2N
AIN
ANSI11000026-5-en-.vsd
71