1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual
Function block type
GOOSESPRCV
GOOSEVCTRRCV
GOOSEXLNRCV
Application
The GOOSE receive function blocks are used to receive subscribed data from the
GOOSE protocol. The validity of the data value is exposed as outputs of the function
block as well as the validity of the communication. It is recommended to use these
outputs to ensure that only valid data is handled on the subscriber IED. An example
could be to control the external reservation before operating on a bay. In the figure
below, the GOOSESPRCV is used to receive the status of the bay reservation. The
validity of the received data is used in additional logic to guarantee that the value has
good quality before operation on that bay.
GOOSESPRCV
Block
Spout
DataValid
CommValid
Test
IEC16000082 V1 EN-US
Figure 224:
GOOSESPRCV and AND function blocks - checking the validity of the
received data
Data Type
Single point
VCTR signals parallel mode
Switch status
AND
Input1
out
Input1
Input2
Noput
Input2
Input3
Input3
Input4
Input4
Section 20
Station communication
GUID-808177B7-02CA-40DF-B41B-8B580E38478B v1
AND
out
Noput
Ext_Res_OK_To_Operate
IEC16000082=1=en.vsd