ABB REC670 Applications Manual page 357

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual
Station HMI
Local
HMI
IED
Apparatus
Apparatus
Control
CLOSE/OPEN
CLOSE/OPEN
breakers disconnectors grounding switches
ANSI08000227 V1 EN-US
Figure 120:
Overview of the apparatus control functions
Features in the apparatus control function:
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchronism check
Pole discrepancy supervision
Operation counter
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks
designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI
Bay control QCBAY
Bay reserve QCRSV
cc
GW
Local
HMI
IED
IED
Apparatus
Control
Control
CLOSE/OPEN
ANSI08000227.vsd