Section 8
Current protection
8.16.2.1
8.16.2.2
236
current and three-phase voltage input in the configuration tool, but it will always
measure the maximum phase current and the minimum phase-to-phase voltage.
VRPVOC (51V) function module has two independent protection each consisting of:
One overcurrent step with the following built-in features:
Selectable definite time delay or Inverse Time IDMT characteristic
Voltage restrained/controlled feature is available in order to modify the pick-
up level of the overcurrent stage in proportion to the magnitude of the
measured voltage
One undervoltage step with the following built-in feature:
Definite time delay
The undervoltage function can be enabled or disabled. Sometimes in order to obtain the
desired application functionality it is necessary to provide interaction between the two
protection elements within the VRPVOC (51V) function by appropriate IED
configuration (for example, overcurrent protection with under-voltage seal-in).
Sometimes in order to obtain the desired application functionality it is necessary to
provide interaction between the two protection elements within the D2PTOC(51V)
function by appropriate IED configuration (for example, overcurrent protection with
under-voltage seal-in).

Base quantities

GlobalBaseSel defines the particular Global Base Values Group where the base
quantities of the function are set. In that Global Base Values Group:
IBase shall be entered as rated phase current of the protected object in primary
amperes.
VBase shall be entered as rated phase-to-phase voltage of the protected object in
primary kV.
Application possibilities
VRPVOC (51V) function can be used in one of the following applications:
voltage controlled over-current
voltage restrained over-current
In both applications a seal-in of the overcurrent function at under-voltage can be
included by configuration.