Tripping Logic Smpptrc (94) - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Section 16
16.1
16.1.1
16.1.2
Bay control REC670 2.2 ANSI
Application manual
Logic

Tripping logic SMPPTRC (94)

Identification
Function description
Tripping logic
Application
All trip signals from the different protection functions shall be routed through the trip
logic. All start signals and directional information can be routed through the trip logic
as well. In its simplest form, the trip logic will only link the TRIP signal to a binary
output and make sure that the pulse time is long enough.
Tripping logic SMPPTRC (94) offers three different operating modes:
Three-pole tripping for all fault types (3p operating mode)
Single-pole tripping for single-phase faults and three-pole tripping for multi-phase
and evolving faults (1p/3p operating mode).
Single-pole tripping for single-pole faults, two-pole tripping for two-pole faults
and three-pole tripping for three-pole faults (1p/2p/3p operating mode).
The logic also issues a three-pole tripping command when phase selection within the
operating protection functions is not possible, or when external conditions request
three-pole tripping. To meet the different double, breaker-and-a-half and other multiple
circuit breaker arrangements, multiple identical SMPPTRC (94) function blocks are
provided within the IED. In such installation, use one instance of SMPPTRC function
per circuit breaker.
If the OHL is connected to the substation via more than one breaker, one SMPPTRC
(94) function block should be used for each breaker. For example when single-pole
IEC 61850
IEC 60617
identification
identification
SMPPTRC
1 -> 0
IEC15000314 V1 EN-US
Section 16
Logic
IP14576-1 v4
SEMOD56226-2 v7
ANSI/IEEE C37.2
device number
94
M12252-3 v10
485

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents