Application Examples - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 14
Control
14.1.3
310
SLGGIO
PSTO
INTONE
NAME1
OFF
NAME2
DL
NAME3
DB
NAME4
DLB
ANSI09000171 V1 EN-US
Figure 107:
Selection of the energizing direction from a local HMI symbol through a
selector switch function block.

Application examples

The synchronism check function block can also be used in some switchyard
arrangements, but with different parameter settings. Below are some examples of how
different arrangements are connected to the IED analog inputs and to the function
block SESRSYN, 25. One function block is used per circuit breaker.
The input used below in example are typical and can be changed by use
of configuration and signal matrix tools.
The SESRSYN and connected SMAI function block instances must
have the same cycle time in the application configuration.
SWPOSN
MENMODE
1MRK 511 401-UUS A
SESRSYN (25)
ANSI09000171_1_en.vsd
Bay control REC670 2.2 ANSI
Application manual
M12323-3 v7