Bay control REC670 2.2 ANSI
Application manual
989_OP = 1
989_CL = 0
989G_OP = 1
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open
state, specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0

Interlocking for breaker-and-a-half diameter BH (3)

Application
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half
diameter according to figure 168.
Section 14
Control
IP14173-1 v3
M13570-3 v6
405