ABB REC670 Applications Manual page 522

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 17
Monitoring
516
Measurement function application for a 380kV OHL
Single line diagram for this application is given in figure 207:
380kV Busbar
800/5 A
380kV 120V
/
kV
3
3
P
Q
380kV OHL
ANSI09000039 V1 EN-US
Figure 207:
Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated
in figure
207
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel PhaseAngleRef
(see Section
"Setting of the phase reference
input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
general settings as shown in table 46.
level supervision of active power as shown in table 47.
calibration parameters as shown in table 48.
IED
ANSI09000039-1-en.vsd
channel") using PCM600 for analog
1MRK 511 401-UUS A
SEMOD54481-12 v11
Bay control REC670 2.2 ANSI
Application manual