Section 14
Control
14.3.1.4
358
The purpose of these functions is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to the primary apparatus
via output boards and to supervise the switching operation and position.
Switches have the following functionalities:
Local/Remote switch intended for the switchyard
Block/deblock for open/close command respectively
Update block/deblock of position indication
Substitution of position indication
Supervision timer that the primary device starts moving after a command
Supervision of allowed time for intermediate position
Definition of pulse duration for open/close command respectively
The realizations of these functions are done with SXCBR representing a circuit breaker
and with SXSWI representing a circuit switch that is, a disconnector or an grounding
switch.
Circuit breaker (SXCBR) can be realized either as three one-phase switches or as one
three-phase switch.
The content of this function is represented by the IEC 61850 definitions for the logical
nodes Circuit breaker (SXCBR) and Circuit switch (SXSWI) with mandatory
functionality.

Proxy for signals from switching device via GOOSE XLNPROXY

The purpose of the proxy for signals from switching device via GOOSE
(XLNPROXY) is to give the same internal representation of the position status and
control response for a switch modeled in a breaker IED as if represented by a SXCBR
or SXSWI function.
The command response functionality is dependent on the connection of the execution
information, XIN, from the SCSWI function controlling the represented switch.
Otherwise, the function only reflects the current status of the switch, such as blocking,
selection, position, operating capability and operation counter.
Since different switches are represented differently on IEC 61850, the data that is
mandatory to model in IEC 61850 is mandatory inputs and the other useful data for the
command and status following is optional. To make it easy to choose which data to use
for the XLNPROXY function, their usage is controlled by the connection of each
data's signal input and valid input. These connections are usually from the
GOOSEXLNRCV function (see Figure
124
and Figure 125).
Bay control REC670 2.2 ANSI
1MRK 511 401-UUS A
GUID-2DA1E47C-5A9A-4C53-8D60-7B1729EF6B90 v1
Application manual