Synchronism check, energizing check, and
synchronizing SESRSYN (25)
Identification
Function description
Synchrocheck, energizing check, and
synchronizing
Application
Synchronizing
To allow closing of breakers between asynchronous networks, a synchronizing feature
is provided. The breaker close command is issued at the optimum time when
conditions across the breaker are satisfied in order to avoid stress on the network and
its components.
The systems are defined as asynchronous when the frequency difference between bus
and line is larger than an adjustable parameter. If the frequency difference is less than
this threshold value the system is defined to have a parallel circuit and the synchronism
check function is used.
The synchronizing function measures the difference between the V-Line and the V-
Bus. It operates and enables a closing command to the circuit breaker when the
calculated closing angle is equal to the measured phase angle and the following
conditions are simultaneously fulfilled: