Integer To Boolean 16 Conversion With Logic Node Representation Itbgapc - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
16.11
Bay control REC670 2.2 ANSI
Application manual
according to the table below from 0 to 32768. This follows the general formula: INx =
x-1
2
where 1≤x≤16. The sum of all the values on the activated INx will be available on
the output OUT as a sum of the values of all the inputs INx that are activated. OUT is
an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it corresponds
to that integer 65535 is available on the output OUT. IB16 function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will
freeze the output at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block IB16.
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
The sum of the numbers in column "Value when activated" when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be
converted to an integer by the IB16 function block.
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
0
Input 11
0
Input 12
0
Input 13
0
Input 14
0
Input 15
0
Input 16
Section 16
Logic
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
8192
0
16384
0
32768
0
SEMOD158419-1 v3