ABB REC670 Applications Manual page 239

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UUS A
Bay control REC670 2.2 ANSI
Application manual
×
1000 200[
MVAr
=
I
r
×
3 400[
kV
]
IEC09000755 V1 EN-US
or on the secondary CT side:
289
A
=
=
I
0.578
r S
_ ec
500 1
IEC09000756 V1 EN-US
Note that the SCB rated current on the secondary CT side is important for secondary
injection of the function.
The parameters for the Capacitor bank protection function CBPGAPC are set via the
local HMI or PCM600. The following settings are done for this function:
General Settings:
Operation =Enabled; to enable the function
IBase =289A; Fundamental frequency SCB rated current in primary amperes. This
value is used as a base value for pickup settings of all other features integrated in this
function.
Reconnection inhibit feature:
OperationRecIn =Enabled; to enable this feature
IRecInhibit =10% (of IBase); Current level under which function will detect that SCB
is disconnected from the power system
tReconnInhibit =300s; Time period under which SCB shall discharge remaining
residual voltage to less than 5%.
Overcurrent feature:
OperationOC =Enabled; to enable this feature
PU 51 =135% (of IBase); Current level for overcurrent pickup. Selected value gives
pickup recommended by international standards.
tOC =30s; Time delay for overcurrent trip
Undercurrent feature:
Operation37 =Enabled; to enable this feature
]
=
289
A
A
Section 8
Current protection
(Equation 89)
(Equation 90)
233