If the input TCINPROG of TCMYLTC or TCLYLTC (84)
function block is connected to the tap changer
mechanism, then this blocking condition will be active if
the TCINPROG input has not reset when the
timer has timed out. The output TCERRAL will be
activated depending on the actual parameter setting. In
correct operation the TCINPROG shall appear during the
VRAISE/VLOWER output pulse and disappear before the
tTCTimeout time has elapsed.
This error condition can be reset by the input RESETERR
on TCMYLTC (84) function block, or alternatively by
changing control mode of TR1ATCC (90) or TR8ATCC
(90) function to Manual and then back to Automatic.