the calculation of circulating currents. The capacitive current is part of the imaginary
load current and therefore essential in the calculation. The calculated circulating
current and the real circulating currents will in this case not be the same, and they will
not reach a minimum at the same time. This might result in a situation when
minimizing of the calculated circulating current will not regulate the tap changers to
the same tap positions even if the power transformers are equal.
However if the capacitive current is also considered in the calculation of the circulating
current, then the influence can be compensated for.
I cc....T2
T1
I
cc....T1
I
T1
I
T1
V
B
I L
Load
V
L
ANSI06000512 V1 EN-US
Figure 177:
Capacitor bank on the LV-side
From figure
177
it is obvious that the two different connections of the capacitor banks
are completely the same regarding the currents in the primary network. However the
CT measured currents for the transformers would be different. The capacitor bank
current may flow entirely to the load on the LV side, or it may be divided between the
LV and the HV side. In the latter case, the part of I
divide between the two transformers and it will be measured with opposite direction
T2
I
T2
I
C
Section 14
I cc....T2
T1
I cc....T1
I
T1
I
I
T1
T2
V
B
I L
Load
V
L
en06000512_ansi.vsd
that goes to the HV side will
C
Control
T2
I
T2
I
C
427