Lon Communication Protocol - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 20
Station communication
20.3
20.3.1
582

LON communication protocol

Application
Station HSI
MicroSCADA
IED
IEC05000663 V2 EN-US
Figure 225:
Example of LON communication structure for a substation automation
system
An optical network can be used within the substation automation system. This enables
communication with the IEDs through the LON bus from the operator's workplace,
from the control center and also from other IEDs via bay-to-bay horizontal
communication. For LON communication an SLM card should be ordered for the
IEDs.
The fibre optic LON bus is implemented using either glass core or plastic core fibre
optic cables.
Table 55:
Specification of the fibre optic connectors
Cable connector
Cable diameter
Max. cable length
Table continues on next page
Gateway
Star coupler
RER 111
IED
IED
Glass fibre
ST-connector
62.5/125 m
1000 m
1MRK 511 401-UUS A
IP14420-1 v1
IP14863-1 v1
M14804-3 v5
Control Center
IEC05000663-1-en.vsd
Plastic fibre
snap-in connector
1 mm
10 m
Bay control REC670 2.2 ANSI