SmartLogger2000-(10-C, 11-C)
User Manual
Figure 4-18 Connecting the SmartLogger to a split EMI (2)
Connecting to a PT100/PT1000 Temperature Sensor over the PT Port
The PT1 port is used as an example.
SmartLogger to the PT100/PT1000.
Issue Draft A (2017-02-15)
One sensor connects to one AI port.
radiation sensor and the SmartLogger. Connections between other sensors and the SmartLogger are
the same.
For details about the cables and cable connection operations, see the documents delivered with the
sensors. The AI port on the SmartLogger is marked + and –. Connect cables correctly according to
the silk screens.
The EMI cannot be automatically identified. After connecting cables, log in to the embedded WebUI
and manually add the EMI. For details, see
and Comm.protocal to AI.
After adding an EMI, set its parameters. For details, see
Setting Running
Parameters.
If the SmartLogger needs to be connected to an EMI and multiple SUN2000s, connect the EMI at
the end of the daisy chain, and verify that the port connected to the EMI has a unique
communications address. For the daisy chain connection, see
Connecting Multiple
SUN2000s.
The SmartLogger provides two PT ports. The PT1 port can connect to a three-wire or two-wire
temperature sensor, whereas the PT2 port can connect to only a two-wire PT100/PT1000
temperature sensor (PT100/PT1000 for short).
If the AI port has been connected to a temperature sensor, the PT port can be reserved.
If the PT1 port connects to a two-wire PT100/PT1000 temperature sensor, you need to short-circuit
the GND port to one – port using the delivered short-circuit cable.
For details about the cables and cable connection operations, see the documents delivered with the
PT100/PT1000. The PT port on the SmartLogger is marked + and –. Connect cables correctly
according to the silk screens.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 4-18
shows only the connection between the solar
7.10.7.1 Connecting
Connection over the AI/PT Port
Figure 4-19
and
Figure 4-20
4 Electrical Connection
Devices. Set Device Type to EMI
in
Daisy Chain Connection
in
show how to connect the
7.7.5.2
4.5.4
51