Huawei SmartLogger2000 User Manual page 17

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
Bottom of the Shell
Figure 2-4 Bottom view of the SmartLogger
Table 2-2 Port description
No.
1
2
3
4
5
6
7
8
9
10
11
Issue Draft A (2017-02-15)
Port (Silk
Function
Screen)
RF1, RF2
Reserved
12V OUT
12 V DC output
12V IN
12 V DC input
USB
USB port
Ethernet optical
SFP1, SFP2
port
ETH1, ETH2
Ethernet electrical
port
DO
Digital parameter
output
COM1–COM
RS485
6
communication
Default
Default key
AC power cable
AC1, AC2
ports
External
grounding
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Description
Reserved.
Provides 12 V DC power supply with a
maximum current of 100 mA.
Connects to a power adapter.
Connects a USB flash drive.
Connects to an ATB or another cascaded
SmartLogger.
Connects to an Ethernet switch, router,
POE module, or PC.
Relay output.
Six RS485 ports that can be connected to
devices such as the SUN2000, box-type
transformer, power meter, or EMI.
Resets and restarts the Bluetooth module or
resets the SmartLogger IP address to the
a
default IP address
. The default IP address
is 192.168.0.10.
SmartLogger2000-10-C: Connects to
the A/B/C three-phase input, and used
for PLC with the SUN2000 over AC
power cables. If PLC function is not
used, you do not have to connect cables
to these ports.
SmartLogger2000-11-C: left blank
N/A
2 Product Overview
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartlogger 2011-cSmartlogger2010-c

Table of Contents