Huawei SmartLogger2000 User Manual page 105

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
No.
Parameter
Description
23
String
Specifies the delay
detection
time for generating
low power
abnormal string
delay
alarms when the
SUN2000 detects that
a PV string is working
with low power. This
parameter is mainly
used in the scenario
where PV strings are
shaded for a long time
in the morning and
evening, and is used
to prevent false
alarms.
24
String
Specifies the delay
detection
time for generating
high power
abnormal string
delay
alarms when the
SUN2000 detects that
a PV string is working
with high power.
25
String
Specifies the
detection
thresholds for
power
determining whether a
segment
PV string is working
division
with high power or
percentage
low power. This
parameter is used to
distinguish the
working status of PV
strings.
String
Specifies the
26
detection
threshold for
reference
determining PV string
asymmetric
exception. The false
coefficient
alarms caused by
fixed shadow shading
can be controlled by
changing this
parameter.
Issue Draft A (2017-02-15)
Default
Unit
Value
min
180
min
30
%
50
N/A
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
[2, 720]
[2, 720]
[1, 100]
SUN2000
SUN2000-(8
-(8KTL-2
KTL-28KTL
8KTL):
): [0.05, 1]
0.2
Others: [5,
Others:
100]
20
7 WebUI
Remarks
This parameter is
displayed when
String monitor is
set to Enable.
This parameter is
displayed when
String monitor is
set to Enable.