Setting A Tracking System - Huawei SmartLogger2000 User Manual

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
No.
Parameter
6
Recovery
gradient of
over
frequency
derating

7.7.3.4 Setting a Tracking System

If a PV string uses a tracking system with controllers, you can set parameters for the tracking
system over the WebUI.
Because of permission restriction, log in as Advanced User. Choose Monitoring >
SUN2000 > Tracking System to access the target page.
Figure 7-24 Setting a tracking system
Issue Draft A (2017-02-15)
Description
Specifies the power
recovery gradient for
overfrequency
derating.
The parameters vary depending on the controller manufacturer. Set parameters based on site
requirements.
This function applies only to the SUN2000-30KTL-A/33KTL/40KTL,
SUN2000-33KTL-JP/40KTL-JP/33KTL-US/36KTL-US/40KTL-US/36KTL/42KTL/43KTL-IN-C1/
50KTL/50KTL-C1, and SUN2000-60KTL-HV-D1.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Default
Unit
Value
%/min
Value Range
Remarks
[5, 20]
This parameter is
set to 16 by
default if the
Australian
AS4777 grid code
is selected, and to
15 by default if
the Italian
CEI0-21 or
CEI0-16 grid
code is selected.