7.9.2.5 Setting Modbus TCP Parameters

Set Modbus TCP parameters to ensure normal communication between the SmartLogger and
a third-party NMS.
Because of permission restriction, log in as Advanced User. Choose Settings > Modbus
TCP to access the target page.
Issue Draft A (2017-02-15)
Set NetEco server to the IP address or domain name of the NetEco server.
When the SmartLogger connects to the Huawei NMS, retain the default value 16100 for Port
number. When the SmartLogger connects to the third-party NMS, set Port number according to
the server port enabled in a third-party NMS.
Set Address mode to Physical address in most cases. When addresses of devices connecting to the
SmartLogger over six RS485 ports are not unique, set Address mode to Logical address.
If SSL encryption is set to Disable, data will be transmitted without being encrypted, which may
result in user data theft. Therefore, exercise caution when deciding to set SSL encryption to
Disable.
If Second challenge authentication is set to Disable, the second challenge authentication result will
not be verified, which may result in user data theft. Therefore, exercise caution when deciding to set
Second challenge authentication to Disable.