SmartLogger2000-(10-C, 11-C)
User Manual
Figure 7-62 Setting email parameters
7.9.4 Port Settings
7.9.4.1 Setting DO Parameters
Context
The SmartLogger provides three DO ports. If one DC power cable of the 3G router is
connected to one of the DO ports in series, power on or off the wireless module by connecting
or disconnecting the DO dry contact to control the reset of the 3G router.
Considering the restrictions on the current that can pass the DO ports of the SmartLogger, you
need to determine the number of DO ports to be used for the control based on the maximum
power supply current of the 3G router (the maximum power supply current can be calculated
based on the maximum power consumption and DC power supply voltage). When the power
supply current is less than 1 A and the voltage is lower than 24 V, use one DO port.
Issue Draft A (2017-02-15)
SMTP Server can be set to the domain name or IP address of the SMTP server.
If it is set to the domain name of the SMTP server, ensure that the address of the DNS server is set
correctly.
SMTP Port specifies the port used for sending emails.
User name and Password specify the user name and password used for logging in to the SMTP
server.
Send address specifies the sender's email address. A maximum of five addresses can be set. Ensure
that the sender's email server is the same as the server specified by SMTP server.
You can click Send test mail to check whether the SmartLogger can successfully send emails to
users.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 WebUI
145