Huawei SmartLogger2000 User Manual page 101

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
No.
Parameter
Description
8
Crystalline
This parameter
silicon PV
reduces the DC
compensati
voltage of PV
on mode
modules to the PE by
reducing the
impedance of the
SUN2000 input side
to the PE, thereby
effectively reducing
PID effect of PV
modules.
9
Communic
The standards of
ation
certain countries and
interrupt
regions require that
shutdown
the SUN2000 must
shut down after the
communication is
interrupted for a
certain time.
10
Communic
Specifies the duration
ation
for determining
interruptio
communication
n duration
interruption, and is
used for automatic
shutdown for
protection in case of
communication
interruption.
Communic
If this parameter is
11
ation
enabled, the
resumed
SUN2000
startup
automatically starts
after communication
recovers. If this
parameter is disabled,
the SUN2000 needs to
be started manually
after communication
recovers.
Issue Draft A (2017-02-15)
Default
Unit
Value
N/A
Output
disabled
N/A
Disable
min
30
N/A
Enable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
Remarks
Output
This parameter is
disabled
displayed if PV
module type is set
P-type output
to Crystalline
N-type
silicon. Set this
output
parameter to P-type
output for P-type
PV modules and
N-type output for
N-type PV modules.
Disable
If Communication
interrupt shutdown
Enable
is set to Enable and
the SUN2000
communication has
been interrupted for
a specified time (set
by Communication
interruption
duration), the
SUN2000 will
automatically shut
down.
[1, 120]
-
Disable
N/A
Enable
7 WebUI
93