SmartLogger2000-(10-C, 11-C)
User Manual
No.
Parameter
Description
12
Soft start
Specifies the duration
time
for the power to
gradually increase
when the SUN2000
starts.
13
AFCI
The North American
standard requires the
SUN2000 to provide
the DC arc detection
function.
14
Arc
Adjusts the sensitivity
detection
of arc detection.
adaptation
mode
15
AFCI
Sends the AFCI
self-test
self-check command
manually.
16
Current
When the IV curves
error
of PV strings are
during
being scanned, the
scanning
current change of PV
strings operating
properly should be
monitored to avoid
inaccurate scanning
caused by sunlight
change. If the current
exceeds the specified
value, it is determined
that the sunlight
changes, and the IV
curves should be
scanned again.
Issue Draft A (2017-02-15)
Default
Unit
Value
s
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
N/A
Enable
N/A
Moderate
N/A
N/A
A
0.20
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
Remarks
[20, 1800]
This parameter is set
to 360 by default if
the Australian
AS4777 grid code is
selected, to 300 by
default if the Italian
CEI0-21 or CEI0-16
grid code is selected,
and to 600 by
default if the
Egyptian EGYPT
grid code is selected.
Disable
This parameter is
supported by only
Enable
the products marked
-US and is set to
Enable by default.
High
This parameter is
displayed only when
Moderate
AFCI is set to
Low
Enable
N/A
[0.00, 2.00]
N/A
7 WebUI
94