Faults

8.1.4 Behaviour in the event of faults

The following generally applies:
1. If works in the danger zone are necessary, the entire plant must be
switched off and protected against an accidental restart.
2. The cause of the fault must be determined.
3. The person responsible for the area in which the fault occurred should
be informed immediately.
4. Depending on the type of fault, the manufacturer may have to be
contacted and will then have the fault removed by an authorized
specialist or will remove the fault themselves.
8.2

Fault and other status messages

Faults (synonymously used here for "alarms") during the operation of the
EK280, can be identified by means of status symbols in the first line of the
display (see chapter 6.3.4).
You can obtain further information and messages under the current status
"Stat" and in the status register "SReg". These can be found:
In the "Cust." register (only "SReg")
Under the path: Admin
Effects and recommended action in the event of fault and status messages:
Message
a) Faults, alarms:
Restart
C-fact. err.
Data error
T Alarm Lim.
Meaning, action
If this message appears whilst in operation, the device
is faulty.
Please contact the Elster support (see chapter 1.3
"Customer service").
The conversion factor could not be calculated as the
measured gas temperature was outside -100°C to
+100°C or no usable compressibility ratio factor was
available.
An error was detected during the cyclic check of the
data subject to calibration regulations.
Please contact the Elster support (see chapter 1.3
"Customer service").
The measured gas temperature is outside the
permissible limits.
The limit values can be changed when putting the
device into operation in the presence of a calibration
officer (see chapter 5.3.1.11, page 55)
Status