Honeywell EK280 Operating Instructions Manual page 93

Volume conversion device
Hide thumbs Also See for EK280:
Table of Contents

Advertisement

Faults
Message
Encoder err.
CDL full
U.Logb. full
online
I2-Rep.sig
I3-Rep.sig
I4-Rep.sig
I5-Rep.sig
I6-Rep.sig
Cal.lock
Admin.lock
Cust.lock o.
Bat. operat.
Dayl.Sav.Tim
Meaning, action
No volume at measurement conditions was recorded at
the connected encoder on input 1 for 20 seconds (with
ext. power supply) or for one measurement cycle + 1
second (battery powered).
The certification data log is full. Changing the
parameters marked with "CDL" without a calibration
lock is only possible if the content of the certification
data log has been deleted.
The software update log is full. An update is only
possible if the content of the software update log has
been deleted.
Data is currently being transmitted via an interface
(modem, optical interface, terminal interface or Ethernet
adapter). If this message is displayed, the "o" will flash
in the "Status" field of the display
(see chapter 6.3.4, page 67).
If an input has been configured as a signal input, this
message will be displayed if an active signal has
appeared at the corresponding terminal (e.g. terminal
DE2).
The input configuration can be adjusted using the
configuration program "enSuite".
The calibration lock is open.
In normal operating conditions, the calibration lock
should be closed to prevent unauthorized changes.
To close the calibration lock, please go to
Ctrl.  St.PL
The administrator / customer lock is open.
The EK280 is in battery mode.
This signal is primarily used to inform a remote data
transmission system that the batteries run down more
quickly during long periods of data transmission.
The time displayed in volume corrector is daylight
saving time.
The switchover mode can be changed using the
configuration program "enSuite".
and enter the value "0".
93